Manual Call Point
Call for Price
Model HCP-E(SCI) is a Manual Call Point with integral short-circuit isolator, which is fully compatible with Hochiki’s ESP analogue addressable protocol. The unit incorporates a bi coloured LED, which can be selected as pulsing/non-pulsing*1 for communications polling and is continuously lit when the HCP-E(SCI) is operated – in these two states the LED will show red. The LED will show amber when a short-circuit is present but will switch to red if the unit is activated. The unit operates by pressing the EN54 compliant non-frangible (plastic) element and produces a high level ESP interrupt. A built in test function initiated by the control panel ensures the integrity of the device at all times and the device can be tested by insertion of a test key in the underside of the unit. Two terminal blocks are provided for easy connection to the loop wiring.
The unit is addressed using the TCH-B100 Hand Held Programmer for quick and reliable addressing. The unit can be flush mounted as supplied. For surface fixing a suitable back box such as the SR MOUNTING BOX is required (sold separately). An optional glass element is also available.
Features
- Fast response Bi-coloured status LED (red for alarm, amber for short-circuit)
- Non-frangible element fitted as standard (conforms to EN54)
- Addressed with TCH-B100 Hand Held Programmer
- Surface or flush mounting (if surface mounting, requires SR MOUNTING BOX – sold separately)
- LPCB Approved to EN54
Specifications
Ordering Code HCP-E(SCI)
Back Box Ordering Code SR MOUNTING BOX (required for surface fixing – sold separately)
Operating Voltage 17 – 41 VDC
Low Power Mode 180 A (max), 100 A (typ)
Quiescent Current 350 A (max), 250 A (typ)
Alarm Current 10.0 mA (max), 5 mA (typ)
Resistance in positive 100 mΩ when closed (max), 100 kΩ when open (min)
Short-circuit threshold (typ) 430 Ω
Transmission Method Digital Communication Using ESP
Operating Temperature Range -10 C to + 50 C
Storage Temperature Range -30 C to + 70 C
Maximum Humidity 95%RH – Non Condensing (at 40 C)
Ingress Protection Rating IP24