Analogue Multi-Sensor ACC-E

Call for Price

In stock

Model ACC-E(HFP) is a Multi-Sensor, which is fully compatible with Hochiki’s ESP
Analogue Addressable Protocol, and incorporates a thermal element and High
Performance photoelectric smoke chamber.
The ACC-E(HFP) has three modes, which are controlled from the Control Panel,
allowing either the optical element or thermal element or both elements to be active
in making the fire decision. The sensor polling LEDs can be controlled via the Control
Panel (pulsing/non-pulsing). The ACC-E(HFP) smoke chamber can easily be removed
or replaced for easy maintenance.

Category:
Features
  • User selectable modes
  • Incorporates Optical & Heat elements
  • Removable, High Performance Chamber
  • Twin LEDs allow 360 viewing – green when polling, turn red in fire
  • Pulsing/non-pulsing controlled from panel*
  • Variable sensitivity
  • Electronically Addressed
  • LPCB & VdS approved to classes A1 & C
  • SIL Level 2 approved variants available
  • Available in white
Specification

Ordering Code          ACC-E(HFP)
Operating Voltage      17 – 41 V d.c.
Low Power Mode      (typ) 120 A
Quiescent Current    (typ) 400 A
Alarm Current (controlled by CIE)        9.1 mA (excluding remote indicator)
Transmission Method       Digital Communications Using ESP
Operating Temperature Range       -10 °C to + 50 °C
Operating Humidity 95%RH           – Non Condensing (at 40 °C)
Storage Temperature Range           -30 °C to +60 °C
Storage Humidity               <80% RH at 60 °C
Colour                           Case Material White / Polycarbonate
Weight (g)     95
Diameter (mm) / Height (mm)           100 / 45
Compatible Bases          YBN-R/3, YBO-R/SCI, YBO-BS, YBO-BSB, YBN-R/3(SCI)
Base Fixing Centres (mm)        48 ~ 74
Approvals                LPCB & VdS approved to classes A1 & C