D2 MPR2
Roll over image to zoom in
Call for Price
Overview
- Sensing both voltage and current signals
- Phase Failure
- Unbalance
- Phase sequence
- Under over voltage
- Overloading and dry running
- Manual Reset
- Delayed auto reset
- Fixed trip settings
- Fixed overload characteristics
- 2CO output relay
Specification
Supply Voltage
- System 380-440V AC ± 20%, 48-63 Hz
- Auxillary 220-240 ± 20% VAC
Output Relay Contact
- Output Relay Contact 2 CO
Trip Setting
- Phase to phase unbalance 50% of Motor Current (Fixed)
- Under current (Dry running)NA 50% of set current (Fixed)
- Overload As per inverse time characteristics
- UV/OV UV = -20% (Fixed) OV = +20% (Fixed)
Trip Time Delay
- On phase failure 4 Sec ± 1%
- For overloading As per Inverse Time Characteristics
2 Sec. (Fixed) - UV/OV RP For UV/OV – 4 Sec ± 1 Sec for RP – Instant
Resetting
- Resetting Delayed Auto
Approx Weight
- Approx Weight 400 gms
Dimensions (mm)
- Overall (L x W x D) 76 x 56.5 x 117.5
- Mounting (L x W) 67 x 46 / 35 mm rail Mounting